Measurements and Calculations Of Earth Electrode Systems (BS 7430)

Please visit our page Chemical Earthings Pipe in Pipe or Chemical Earthings Strip in Pipe for detailed information on earthings.

1. Nature of site

The basic nature and properties of soil in a given location cannot be changed without considerable expense, and careful consideration of the geology should be used to determine the best location for an earthing system.

Where there is an option, a site should be chosen in one of the following types of situations in the order of preference given:

  1. Wet marshy ground;
  2. Clay, loamy soil, arable land, clayey soil, clayey soil or loam mixed with small quantities of sand;
  3. Clay and loam mixed with varying proportions of sand, gravel, and stones;
  4. Damp and wet sand, peat.
Dry sand, gravel, chalk, limestone, whinstone, granite, any very stony ground, and all locations where virgin rock is very close to the surface should be avoided if possible. A site should be chosen where the moisture content is ideally continuously within the range of 15% to 20%. A waterlogged location is not essential unless the soil is sand or gravel.

Care should be taken to avoid a site where water flows over it (e.g. the bed of a stream) for the beneficial salts can be entirely removed from the soil in such situations.

1.1 Soil treatment

In high resistivity locations or on rocky ground where long term performance is required, it may be considered necessary to utilize a conductive concrete to improve earth contact resistance around an earth rod or strip (tape) where applicable.

There are commercially available materials to achieve this effectively, but care should be taken to understand how they work during installation to ensure that they remain in contact with the rod or strip and do not shrink or swell away after drying out.

Chemical treatment of soil has environmental implications and should not be considered as a long term solution in order to meet a specified level of resistance, apart from the risk of corrosion to the earthling system. Coke breeze should also not be used due to its highly corrosive nature.

Trench method of soil treatment

2. Soil resistivity

The resistance to earth of a given electrode depends upon the electrical resistivity of the soil. Most first approximation formulae are related to homogenous soil, which is rarely the case in practice, where the different layers of strata will affect the distribution of current passing through the electrode.

Table 1 gives examples of resistivity only. These figures are very general and should not be used to replace actual measurements made at the proposed site. They may be used to give an indication of the difficulties that one might face in preparing an adequate design at the chosen location.

The effective resistivity is also controlled by the mineral salts in the ground and the level of moisture content, which is why it should be remembered that readings taken long after installation can vary considerably from the original test results.

Soil temperature has some effect on the upper layers of strata, but is only important under frosty conditions. Therefore any part of an electrode system which is less that 0.5 m below ground level should not be considered to be effective.

Table 1 – Examples of soil resistivity in Ωm

Examples of soil resistivity in Ωm



3. Measurement of soil resistivity

Soil resistivity may be measured in a similar manner to the establishment of the resistance of the earth electrode.

Measurements of the soil resistivity for the pre-determination of the resistance to earth or the impedance to earth should be carried out using a four probe method (widely known as the Wenner method) as follows.
  1. Drive four equally spaced test electrodes to a depth of not greater 5% of their spacing apart a. It is important to ensure that their resistance areas do not overlap (Figure 2)
  2. Pass current between the two outer electrodes
  3. Measure the earth potential between the two inner electrodes

The resistance R should be taken as the ratio of the voltage between the inner electrodes and the current between the outer electrodes. In homogenous soil the average resistivity ρ in ohm metres (Ωm) may be taken as:

ρ = 2 π a R

where:

  • a is the spacing between electrodes, in metres (m);
  • R is the resistance measured between the middle electrodes, in ohms (Ω).
Measurement of earth resistivity

Figure 2 – Measurement of earth resistivity

The resistivity so determined applies to an electrode separation distance a, which is related to the depth of investigation. By repeating the measurement with increasing values of a, the apparent resistivity involving greater depths may be assessed.

This may be taken as an indication of the possible gain from driving deeper rods, etc., into strata of a lower resistivity to get the required resistance.

Four equally spaced test spikes should be driven to a depth of up to 1 m, the depth not exceeding 5% of their separation a.

It is important to ensure that their resistance areas do not overlap. Current should be passed between the two outer electrodes and the resistance R may be found as the ratio of the voltage between the inside electrodes to the current conducted through the outside electrodes.

The resistivity found applies to soil depth a, so by repeating the measurement with different values of a, the average resistivity to various depths may be found and the results indicates whether any advantage is to be gained by installing deeply driven electrodes in order to reach strata of a lower resistivity.

EXAMPLE – If the distance a between electrodes is 1 m the constant for the test setup is calculated as (2 × 3.14 × 100) cm =  628 cm. If the instrument reads 40 Ω the earth resistivity is (40 × 628) Ωcm = 25 120 Ωcm.

It should be noted that environmental conditions such as temperature have an impact on earth resistivity with a corresponding decrease in resistivity as temperature rises.

4. Types of earth electrodes and their resistance calculation

An earthing system should be of the highest integrity and of robust construction to ensure that it remains safe and will not endanger the health and safety of persons or their surroundings. The majority of the formulae presented in this section relate to low frequency currents and high frequency examples are not included.

It is therefore important to recognize this issue if a long horizontal tape or bare cable is being considered for producing a low earth resistance, even though the impedance will ultimately be limited to a final value (see Figure 4).

Earthing systems should consist of copper conductors, copper clad or austenitic steel rods of appropriate dimensions, cast iron plates, or steel piles used individually or connected together in combination to form a single local earth electrode system.

Impedance to earth of horizontal earth electrodes buried in homogeneous soil

Figure 4 – Impedance to earth of horizontal earth electrodes buried in homogeneous soil
 

The formulae which follow are all based on homogeneous soil conditions, so in most practical situations only give a reasonable idea of the problems (within 15% accuracy) that might exist if the strata is such that the resistivity changes at different levels.

It may be considered necessary to apply numerical methods which are more complex than the formulae given below and software is available to carry out the more detailed calculations. The results from the formulae below are within 10% to 15% accuracy and may be assumed to be sufficient for guidance on what might be the outcome of a given design.

However, onsite resistivity testing should always be carried out prior to carrying out an earth system design and installation.

The effect of shape on an electrode resistance is related to the current density around the particular electrode considered. To obtain a low overall resistance the current density should be as low as possible in the medium surrounding the electrode.

This may be achieved by making the dimensions in one direction large by comparison to the other two. Thus a pipe rod or strip has a much lower resistance than a plate of equal surface area.

a) Plates

The approximate resistance to earth of a plate R in ohms (Ω) may be calculated from:

The approximate resistance to earth of a plate R in ohms (Ω)

where:

  • ρ is the resistivity of the soil (assumed uniform), in ohm metres (Ωm);
  • A is the area of one face of the plate, in square metres (m2).

Plates, if used, should be installed as small units of not greater than 1.2 m × 1.2 m connected in parallel vertically and at least 2 m apart. The minimum ground cover should not be less than 600 mm and ideally the surrounding soil should be damp.

Connections to the plate should be by copper conductor, welded, riveted or otherwise attached with material that will not cause corrosion at the joint. The finished joint should be covered with a heavy coat of bitumen. The connecting strip to the above ground disconnection point should be fully insulated to avoid electrolytic action.

Where the plate is placed in a cut out slot, e.g. in a chalk bed near the surface, the slot should be big enough to allow at least 300 mm thickness of soil or other conducting low resistivity medium cover around the whole plate. This requires careful assembly during installation to ensure that the bottom of the plate is resting in the medium used and not on the chalk or high resistivity substrata.

NOTE! For conventional sizes, the resistance is approximately inversely proportional to the linear dimensions, not to the surface area, i.e. a 0.9 m × 0.9 m plate has a resistance approximately 25% higher than a 1.2 m × 1.2 m plate.

b) Rod electrode

The resistance of a rod Rr in ohms (Ω) may be calculated from:

The resistance of a rod Rr in ohms (Ω)

where:

  • ρ is the resistivity of soil, in ohm metres (Ωm);
  • L is the length of the electrode, in metres (m);
  • d is the diameter of the rod, in metres (m).

NOTE! – Change of diameter has little effect on the overall value of resistance, and the size is more governed by the mechanical strength of the rod to withstand being mechanically driven when deep earth rods are required e.g. to depths of 20 m or more.

c) Strip or round conductor electrodes

This section deals only with a straight run of conductor. Other shapes are not covered here.The resistance Rta in ohms (Ω) of a strip or round conductor may be calculated from:

The resistance of strip or round conductor electrodes

where:

  • ρ is the resistivity of soil, in ohm metres (Ωm);
  • L is the length of the electrode, in metres (m);
  • h is the depth of the electrode, in metres (m);
  • d is the diameter of the round conductor or diameter of the equivalent cross sectional area of the strip, in metres (m).

When two or more strips in straight lengths, each of length L in meters (m) and a separation distance s metres are laid parallel to each other and connected together at one end only the combined resistance may be calculated from the following equation:

Rn = F R1

where:

  • Rn is the resistance of n conductors in parallel, in ohms (Ω)
  • R1 is the resistance of a single strip of length L, calculated from the preceding Rta equation, in ohms (Ω).
  • F has the following value:
    • For two lengths: F = 0.5 + [0.078(s/L)] − 0.307
    • For three lengths: F = 0.33 + [0.071(s/L)] − 0.408
    • For four lengths: F = 0.25 + [0.067(s/L)] − 0.451
    • Provided that 0.02 < (s/L) < 0.3

d) Mesh

The resistance of a mesh (grid) Rm ohms (Ω) may be calculated from:

The resistance of a mesh (grid)

Where:

  • ρ is the resistivity of soil, in ohm metres (Ωm);
  • A is the actual area covered by the mesh, in square metres (m2);
  • L is the total length of strip used in the mesh, in metres (m).

e) Resistance of an electrode encased in low resistivity material, e.g. conducting concrete

The resistance of a backfilled electrode Rb in ohms (Ω) may be calculated from:

Resistance of an electrode encased in low resistivity material

where:

  • ρ is the resistivity of soil, in ohm metres (Ωm);
  • ρc is the resistivity of the conducting material used for the backfill, in ohm metres (Ωm);
  • L is the length of rod, in metres (m);
  • d is the diameter of the rod, in metres (m).


Leave a Reply

Your email address will not be published. Required fields are marked *